KNX LED Controller 3 Channels constant voltage TYB673A

EAN
3250617579551
Packaging
1 Piece

Technical properties

Archi­tec­ture
  • Bus system
    KNX
  • Fixing mode
    flush-­mounting
Func­tions
  • Number of func­tion chan­nels
    3
  • Bus module detach­able
    No
Config­ur­a­tion
  • Number of modules
    0
Controls and indic­ators
  • Indic­ator lamp
    yes
  • Button / push-button
    with program­ming button and red program­ming LED
Main elec­trical features
  • Rated current
    12 mA
Voltage
  • Input voltage
    12…24 V DC
  • Oper­ating voltage over bus
    21…32 V DC
Elec­tric current
  • Bus current consump­tion (data trans­fer)
    max. 12 mA
  • Maximum through current
    2 A
  • Output current per channel
    max. 2.2 A
Fuse
  • Fuse
    over­heating protec­tion (dis­play using LEDs)
Dimen­sions
  • Width of rail mounted device (RMD)
    0 modules
Incan­des­cent bulbs control
  • Max. power with incan­des­cent lamps
    155 W
Connec­tion
  • Conductor cross-sec­tion (flex­ible)
    0.75…1.5 mm²
  • Conductor cross-sec­tion (rigid)
    0.75…1.5 mm²
  • Bus coup­ling unit
    with integral bus coup­ling unit
  • Type of connec­tion
    with screw terminals
  • Bus connec­tion
    bus connec­tion via connecting terminal
Cable
  • Load cable length
    max. 10 m
Settings
  • Supported config­ur­a­tion modes
    system
Scope of delivery
  • Bus connec­tion included
    Yes
Equip­ment
  • Number of outputs
    1
  • Number of inputs
    1
  • Substa­tion input
    No
  • Modular expand­ab­ility
    No
  • Dimming prin­ciple
    with pulse width modu­la­tion (PWM)
  • Inter­face 1-10 V
    No
Use
  • Differ­en­ti­ation char­ac­ter­istic 3 - Sales
    with screw terminals
Safety
  • Protec­tion index IP
    IP20
Use condi­tions
  • Oper­ating temper­ature
    -5…45 °C
  • Stor­age/trans­port temper­ature
    -20…70 °C
Iden­ti­fic­a­tion
  • Main design line
    KNX
Instruc­tions
  • Special note text
    The power supply selected must be compat­ible with the load connected to the device. ; Caution! Connected loads depend on external LED power supply. Observe manu­fac­turer's data.

Downloads

  • Images

    Images may be subject to copyright

    Image TYB673A  | Hager

    Product Image TYB673A

  • ProductNotice

    Image Instruction manuals for TYB673A  | Hager

    Instruction manuals for TYB673A

    PDF
    689 KB
  • ProductETSBase

    Image Product-Database ETS for TYB673A  | Hager

    Product-Database ETS for TYB673A

    ETS Database for TYB673A

    KNXPROD
    76 KB
  • ProductApplicationDescription

    Image Application guides ETS / easy link for TYB673A  | Hager

    Application guides ETS / easy link for TYB673A

    Application description TYB673A_B

    PDF
    1 MB
More documentation