LVSG00SP

LVSG00SP Fuse switch vert. size 00 185 3P M8

LVSG00SP

Fuse switch vert. size 00 185 3P M8

Cat ref.:LVSG00SP
prt.
EAN No.:

4049857199853

P.U.:1 prt.
Technical Characteristics
Number of poles:3 P
Frequency:50/60 Hz
Rated operational voltage Ue:0/690 V
Rated insulation voltage:1000 V
Overvoltage category according to IEC 60947-1 2.5.60 Table 1:IV-supply system level (feed)
Rated impulse withstand voltage:8 kV
Cut off current:120 kA
Rated current for Ue=400V AC according to IEC 61439-1 5.3.2:160 A
Rated current for Ue=500V AC according to IEC 61439-1 5.3.2:160 A
Rated current for Ue=690V AC according to IEC 61439-1 5.3.2:160 A
Rated short-time withstand current 1s:5 kA
Rated conditional short-circuit current for Ue=400V IEC 61439-1 3.8.10.4:120 kA
Rated conditional short-circuit current for Ue=500V IEC 61439-1 3.8.10.4:120 kA
Rated conditional short-circuit current for Ue=690V IEC 61439-1 3.8.10.4:100 kA
Fuse-links test rated cond. short-circuit current Ue=400V IEC 61439-1 3.8.10.4:160 A
Fuse-links test rated cond. short-circuit current Ue=500V IEC 61439-1 3.8.10.4:160 A
Fuse-links test rated cond. short-circuit current Ue=690V IEC 61439-1 3.8.10.4:160 A
Conv. free air therm.current w/fuse-links and std.cross sect. IEC60947-1 4.3.2.1:160 A
Conventional free air thermal current with Trennmesser and std. cross section:220 A
Rating current 40°C:160 A
Rating current 45°C:152 A
Rating current 50°C:144 A
Rating current 55°C:136 A
Rating current 60°C:128 A
Rating current 65°C:120 A
Rating current 70°C:112 A
Fuse Size:NH00
Loss power at full load:≈ 58 W
Maximum Power loss of the Fuse-Link installed in device:12 W
Total power loss under IN:22 W
Dissipated energy in cable:38,46 W
Electric endurance in number of cycles:200
Total service life (mechanical and electrical endurance) IEC 60947-3 Table 4:1600
Number of mechanical operations:1400
Copper weight of the product:800 g
Silver weight of the product:1,37 g
Height of installed product:123 mm
Length:741 mm
Width of installed product:50 mm
Entre-axe between bars of busbars:185 mm
Tightening torque:14Nm
Torque at mounting on busbar:14 Nm
Connection cross-sect. rigid cable:2,5 / 95mm²
Connection cross-sect. flexible conductor:2,5 / 95mm²
Type of connection:screw
Operation of switching devices according to IEC 60947-1 2.4:depending manual operation (of a mechanical switching device)
Rated duties according to IEC 60947-1 4.3.4:Continuous operation
Standard cross section according to IEC 60947-1 Tables 9 and 10:70 mm²
Utilisation category for Ue=400V AC according to IEC 60947-3 Table 5:AC-23B
Utilisation category for Ue=500V AC according to IEC 60947-3 Table 5:AC-22B
Utilisation category for Ue=690V AC according to IEC 60947-3 Table 5:AC-22B
European directive WEEE:concerned
Protection index IP:IP3X
Degree of pollution according to IEC 60664 / IEC 60947-2:3
Storage temperature:-40 to 70 °C
Max. temperature connected below with Fuse-Links IEC 60947-1 Table 2:42 K
Max. temperature connected below with Solid-links IEC 60947-1 Table 2:62 K
Max. Busbar temperature with Fuse-Links IEC 60947-1 Table 2:32 K
Max. Busbar temperature with Solid-links IEC 60947-1 Table 2:42 K
Weight:2,099 kg
  • LVSG00SP
    LVSG00SP Fuse switch vert. size 00 185 3P M8
    LVSG00SP
  • LVSG00SP Fuse switch vert. size 00 185 3P M8
Data is subject to errors and technical modifications.