KNX room cont., colourdisplay, intg bus coupling unit, KNX 80660100

EAN
4011334415930
Packaging
1 Piece

Technical properties

Archi­tec­ture
  • Fixing mode
    flush-­mounting
Func­tions
  • Easy link func­tions
    switching of scenes (1..8) possible ; oper­ating mode heat­ing, cooling or heat­ing/­cooling can be selected ; switching PI-con­trol (PWM) or switching 2-point control can be selected ; heating type warm water heat­ing, warm water under­floor heat­ing, elec­tric heat­ing, elec­tric under­floor heating or split unit can be selected ; cooling type cooling ceil­ing, convector fan or split unit can be selected ; comfort, standby, night-­time reduc­tion, frost/heat protec­tion oper­ating mode switch­able via scene
  • Func­tion
    with keylock ; with holiday switching ; with frost protec­tion func­tion
  • Func­tion
    oper­ating modes heat­ing, cool­ing, heat­ing/­cooling or back­ground heating and addi­tional heat­ing/­cooling can be selected ; control modes switching PI-con­trol (PWM), continuous PI control or switching 2-point control can be selected ; heating types warm water heat­ing, warm water under­floor heat­ing, elec­tric heat­ing, elec­tric under­floor heat­ing, split unit or adjustable via object
Controls and indic­ators
  • Oper­a­tion
    Oper­a­tion via sens­itive Touch control surface
  • Indic­a­tion / display
    display of set or actual temper­ature ; Screen saver ; LC display with symbol display ; Time and date display ; to display and initiate actions
Voltage
  • Auxil­iary voltage
    24 V DC
  • Oper­ating voltage over bus
    21…32 V DC
Elec­tric current
  • Current consump­tion (oper­a­tion)
    25 mA
  • Bus current consump­tion (data trans­fer)
    max. 10 mA
Dimen­sions
  • Inser­tion depth
    32 mm
  • Dimen­sions of display (W x H)
    38.28 x 30.26 mm
  • Width of rail mounted device (RMD)
    0 modules
  • Width
    71 mm
Screen
  • TFT screen size
    1.93 ″
Install­a­tion, mounting
  • Install­a­tion mode
    with spreader claws ; for flush-­mounted and hollow-wall mounting ; for single mounting ; for vertical mounting
Connec­tion
  • Bus coup­ling unit
    with integral bus coup­ling unit
  • Bus connec­tion
    bus connec­tion via connecting terminal
  • Connec­tion
    with addi­tional connec­tion for external floor temper­ature sensor/re­mote sensor
Settings
  • Supported config­ur­a­tion modes
    system, easy
  • Time
    with auto­matic summer­/winter time change-over
Equip­ment
  • Heating
    for heating and/or cooling mode ; heating or cooling possible in 2 stages
  • Control
    for indi­vidual single room temper­ature control ; control para­meter for heating / cooling unit pre-set
Use
  • Differ­en­ti­ation char­ac­ter­istic 2 - Sales
    with colour display
  • Differ­en­ti­ation char­ac­ter­istic 3 - Sales
    integ­rated bus coup­ling unit
Safety
  • REACH conform
    No
  • Halogen free
    No
Use condi­tions
  • Oper­ating temper­ature
    -5…45 °C
  • Stor­age/trans­port temper­ature
    -20…70 °C (storage at > 45°C reduces the service life)
  • Temper­ature
    comfort, standard and night temper­ature ; temper­ature meas­ure­ment via internal and/or connect­able temper­ature sensor with average determ­in­a­tion ; addi­tional connec­tion for external temper­ature sensor
  • Energy effi­ciency class
    IV (2%)
Iden­ti­fic­a­tion
  • Applic­a­tion, usage
    KNX - oper­ating systems
  • Product family
    Product family: heat­ing, vent­il­a­tion, air condi­tioning
  • Compos­i­tion
    basis element
  • Main design line
    KNX
Instruc­tions
  • Inform­a­tion text
    The KNX room controller in compar­ison with the ther­mo­stat also has push-button func­tions and can thus control all subsys­tems in a room.