MCB 2P 10kA C-1A 2M NCN201

EAN
3250614614705
Packaging
6 PCEs

Technical properties

Archi­tec­ture
  • Neutral posi­tion
    without neutral
  • Number of protected poles
    2
  • Number of poles
    2 P
  • Type of pole
    2 P
  • Curve
    C
Func­tions
  • Concur­rently switching N-neutral
    No
Config­ur­a­tion
  • Number of modules
    2
Connectivity
  • Top connec­tion aligne­ment for modular devices
    Aligned terminal
  • Bottom connec­tion aligne­ment for modular devices
    Aligned terminal
Main elec­trical features
  • Rated short circuit breaking capa­city Icn AC according IEC60898-1
    10 kA
  • Rated oper­a­tional voltage Ue
    415 V
  • Type of supply voltage
    AC
Voltage
  • Rated insu­la­tion voltage
    500 V
  • Max oper­ating voltage
    440 V
  • Rated impulse with­stand voltage
    6000 V
  • Minimum threshold voltage (Ue min)
    12 V
Elec­tric current
  • Rated current
    1 A
  • Rated service breaking capa­city Ics AC according IEC 60898-1
    7.5 kA
  • min/maxi threshold value of the AC thermal oper­a­tion
    1.13 / 1.45 In
  • Magnetic regu­lating currrent
    5 / 10 In
  • min/maxi threshold value of the DC magnetic oper­a­tion
    7 / 15 In
  • min/maxi threshold value of the DC thermal oper­a­tion
    1.13 / 1.45 In
  • Rating current -10°C according to IEC 60947
    1.5 A
  • Rating current -15°C according to IEC 60947
    1.53 A
  • Rating current -20°C according to IEC 60947
    1.57 A
  • Rating current -25°C according to IEC 60947
    1.6 A
  • Rating current -5°C according to IEC 60947
    1.46 A
  • Rating current 0°C according to IEC 60947
    1.43 A
  • Rating current 10°C according to IEC 60947
    1.35 A
  • Rating current 15°C according to IEC 60947
    1.31 A
  • Rating current 20°C according to IEC 60947
    1.27 A
  • Rating current 25°C according to IEC 60947
    1.23 A
  • Rating current 30°C according to IEC 60947
    1.19 A
  • Rating current 35°C according to IEC 60947
    1.15 A
  • Rating current 40°C according to IEC 60947
    1.1 A
  • Rating current 45°C according to IEC 60947
    1.05 A
  • Rating current 5°C according to IEC 60947
    1.39 A
  • Rating current 50°C according to IEC 60947
    1 A
  • Rating current 55°C according to IEC 60947
    0.95 A
  • Rating current 60°C according to IEC 60947
    0.89 A
  • Rating current 65°C according to IEC 60947
    0.83 A
  • Rating current 70°C according to IEC 60947
    0.76 A
  • Rated short circuit breaking capa­city Icn under 230V AC according IEC60898-1
    10 kA
  • Rated short circuit breaking capa­city Icn under 400V AC according IEC60898-1
    10 kA
  • Rated ulti­mate short-­cir­cuit breaking capa­city Icu under 230V AC IEC 60947-2
    30 kA
  • Rated ulti­mate short-­cir­cuit breaking capa­city Icu under 240V AC IEC 60947-2
    30 kA
  • Rated ulti­mate short-­cir­cuit breaking capa­city Icu under 400V AC IEC 60947-2
    15 kA
  • Rated ulti­mate short-­cir­cuit breaking capa­city Icu under 415V AC IEC 60947-2
    15 kA
  • Rated short circuit breaking capa­city Icn under 240V AC according IEC 60898-1
    10 kA
  • Rated short circuit breaking capa­city Icn under 415V AC according IEC 60898-1
    10 kA
  • Rated ulti­mate short-­cir­cuit breaking capa­city Icu under 220V AC IEC 60947-2
    30 kA
  • Rated ulti­mate short-­cir­cuit breaking capa­city Icu under 380V AC IEC 60947-2
    15 kA
Elec­tric current / temper­ature
  • Rating current -25°C
    1.34 A
  • Rating current -20°C
    1.32 A
  • Rating current -15°C
    1.29 A
  • Rating current -10°C
    1.26 A
  • Rating current -5°C
    1.23 A
  • Rating current 0°C
    1.2 A
  • Rating current 5°C
    1.17 A
  • Rating current 10°C
    1.14 A
  • Rating current 25°C
    1.04 A
  • Rating current 30°C
    1 A
  • Rating current 35°C
    0.96 A
  • Rating current 40°C
    0.92 A
  • Rating current 45°C
    0.88 A
  • Rating current 50°C
    0.84 A
  • Rating current 55°C
    0.8 A
  • Rating current 60°C
    0.75 A
  • Rating current 65°C
    0.7 A
  • Rating current 70°C
    0.64 A
Current correc­tion factors
  • Correc­tion factor of rating current for 2 devices placed side-by-side
    1
  • Correc­tion factor of rating current for 3 devices placed side-by-side
    0.95
  • Correc­tion factor of rating current for 4 and 5 devices placed side-by-side
    0.9
  • Correc­tion factor of rating current for 6 devices placed side-by-side
    0.85
  • Correc­tion factor of magnetic trip­ping with 100 Hz
    1.1
  • Correc­tion factor of magnetic trip­ping with 200 Hz
    1.2
  • Correc­tion factor of magnetic trip­ping with 400 Hz
    1.5
  • Correc­tion factor of magnetic trip­ping with 60 Hz
    1.1
Dimen­sions
  • Depth of installed product
    70 mm
  • Height of installed product
    83 mm
  • Width of installed product
    35 mm
Frequency
  • Frequency
    50 to 60 Hz
Power
  • Maximum power loss per pole according to the product standard
    3 W
  • Total power loss under IN
    2.11 W
  • Power loss per pole at In
    1.06 W
Endur­ance
  • Elec­tric endur­ance in number of cycles
    4000
  • Number of mech­an­ical oper­a­tions
    20000
Install­a­tion, mounting
  • Type of top connec­tion for modular devices
    with screw
  • Tight­ening torque
    2,8Nm
  • Type of top rail clip for modular devices
    NA
  • Type of bottom rail clip for modular devices
    plastic
  • Type of Bottom Connec­tion for modular devices
    BIcon­nect
  • Top remov­ab­ility for modular devices
    Yes
  • Bottom remov­ab­ility for modular devices
    Yes
  • Suit­able for flush-­mounting
    Yes
Connec­tion
  • Connec­tion cross-sec­tion at output with screw, for flex­ible conductor
    1 / 25 mm²
  • Connec­tion cross-sec­tion at output with screw, for massive conductor
    1 / 35 mm²
  • Connec­tion cross-sec­tion for rigid conductor, upstream terminals with screws
    1 / 35 mm²
  • Connec­tion cross-sec­tion of the access with screws, with flex­ible conductor
    1 / 25 mm²
  • Down­stream cage clamp delivery status
    closed
  • Upstream cage clamp delivery status
    opened
Equip­ment
  • Can be access­or­ized
    Yes
Stand­ards
  • Standard text
    EN 60898-1
  • European directive WEEE
    concerned
Safety
  • Protec­tion index IP
    IP20
Use condi­tions
  • Oper­ating temper­ature
    -25…70 °C
  • Degree of pollu­tion according to IEC 60664 / IEC 60947-2
    2
  • Class of energy limit­a­tion I²t
    3
  • Alti­tude
    2000 m
  • Stor­age/trans­port temper­ature
    -25…80 °C
temper­atur
  • Temper­ature of calib­ra­tion
    30 °C

Downloads

  • Images

    Images may be subject to copyright

    Image NCN201  | Hager

    Product Image NCN201

  • ProductECDeclaration

    Image EU Declaration of conformity for NCN201  | Hager

    EU Declaration of conformity for NCN201

    Declaration

    PDF
    710 KB
  • ProductEnvironmentProfile

    Image Product environmental profile for NCN201  | Hager

    Product environmental profile for NCN201

    PDF
    432 KB
More documentation