LVSG1CPX

LVSG1CPX Fuse switch vert. size 1 3p M12

LVSG1CPX
LVSG1CPX Fuse switch vert. size 1 3p M12
Product Drawing Vertical type

Fuse switch vert. size 1 3p M12

Cat ref.:LVSG1CPX
prt.
EAN No.:

4049857124817

P.U.:1 prt.
Technical Characteristics
Number of poles:3 P
Type of pole:3 P
Frequency:50/60 Hz
Rated operational voltage Ue:0/690 V
Rated insulation voltage:1000 V
Overvoltage category according to IEC 60947-1 2.5.60 Table 1:IV-supply system level (feed)
Rated impulse withstand voltage:12 kV
Acceptable current rating with AC22 category B:250 A
Acceptable current rating with AC23 category B:250 A
Cut off current:120 kA
Rated current for Ue=400V AC according to IEC 61439-1 5.3.2:250 A
Rated current for Ue=500V AC according to IEC 61439-1 5.3.2:250 A
Rated current for Ue=690V AC according to IEC 61439-1 5.3.2:250 A
Rated short-time withstand current 1s:10 kA
Rated conditional short-circuit current for Ue=400V IEC 61439-1 3.8.10.4:120 kA
Rated conditional short-circuit current for Ue=500V IEC 61439-1 3.8.10.4:120 kA
Rated conditional short-circuit current for Ue=690V IEC 61439-1 3.8.10.4:100 kA
Fuse-links test rated cond. short-circuit current Ue=400V IEC 61439-1 3.8.10.4:250 A
Fuse-links test rated cond. short-circuit current Ue=500V IEC 61439-1 3.8.10.4:250 A
Fuse-links test rated cond. short-circuit current Ue=690V IEC 61439-1 3.8.10.4:200 A
Conv. free air therm.current w/fuse-links and std.cross sect. IEC60947-1 4.3.2.1:250 A
Conventional free air thermal current with Trennmesser and std. cross section:320 A
Rating current 40°C:250 A
Rating current 45°C:237,5 A
Rating current 50°C:225 A
Rating current 55°C:212,5 A
Rating current 60°C:200 A
Rating current 65°C:187,5 A
Rating current 70°C:175 A
Fuse Size:NH1
Loss power at full load:≈ 96 W
Maximum Power loss of the Fuse-Link installed in device:23 W
Total power loss under IN:27 W
Dissipated energy in cable:50,44 W
Electric endurance in number of cycles:200
Total service life (mechanical and electrical endurance) IEC 60947-3 Table 4:1600
Number of mechanical operations:1400
Copper weight of the product:1699 g
Silver weight of the product:2,18 g
Depth of installed product:190 mm
Height of installed product:125 mm
Length:665 mm
Width of installed product:100 mm
Entre-axe between bars of busbars:185 mm
Tightening torque:32Nm
Torque at mounting on busbar:32 Nm
Type of connection:Screw connection
Operation of switching devices according to IEC 60947-1 2.4:depending manual operation (of a mechanical switching device)
Rated duties according to IEC 60947-1 4.3.4:Continuous operation
Standard cross section according to IEC 60947-1 Tables 9 and 10:120 mm²
Utilisation category for Ue=400V AC according to IEC 60947-3 Table 5:AC-23B
Utilisation category for Ue=500V AC according to IEC 60947-3 Table 5:AC-22B
Utilisation category for Ue=690V AC according to IEC 60947-3 Table 5:AC-21B
European directive WEEE:concerned
Protection index IP:IP2X
Degree of pollution according to IEC 60664 / IEC 60947-2:3
Storage temperature:-40 to 70 °C
Max. temperature connected below with Fuse-Links IEC 60947-1 Table 2:56 K
Max. temperature connected below with Solid-links IEC 60947-1 Table 2:65 K
Max. Busbar temperature with Fuse-Links IEC 60947-1 Table 2:42 K
Max. Busbar temperature with Solid-links IEC 60947-1 Table 2:48 K
Weight:4,51 kg
  • LVSG1CPX
    LVSG1CPX Fuse switch vert. size 1 3p M12
    LVSG1CPX
  • LVSG1CPX
    Product Drawing Vertical type
  • LVSG1CPX Fuse switch vert. size 1 3p M12
  • Product Drawing Vertical type
Data is subject to errors and technical modifications.